GENERAL INFO & MAIN BENEFITS
The AWRMS™ 200 is a computer controlled test system developed for measuring Transformer Resistance and for performing Heat Run Tests in highly inductive loads. A single source with a 100 Vdc test voltage is used to saturate even the largest transformer within seconds. A heavy-duty protection circuit dissipates the stored magnetic energy rapidly after the test. An automatic Tap Changer speeds up the measurement of all the windings. Optimum accuracy for the resistance measurements is achieved using the four-wire principle of resistance measurement.
The AWRMS™ 200 is capable of measuring the resistance of up to three windings connected in series simultaneously. The DC current of the 25 kW supply is continuously adjustable up to 200 A for testing windings in large transformers, electric motors, generators and reactors.
Up to 40 temperature channels consisting of PT100s or Thermocouples can be supplied.
INDUSTRY APPLICATIONS
The AWRMS™ system is primarily used for:
• Transformer and Rotating Machinery Manufacturers.
• Power Utilities.
• Electric Contractors.
• Government and Private Labs, and Service or Maintenance Companies.
SYSTEM APPLICATIONS
The AWRMS™ 200 is capable of the testing both three-phase (Y-Wye, Δ-Delta, or Mixed) and single-phase power subsystems [(VA to MVA); (fractional HP to kHP or W to MW)]:
• Electric Motors, Generators, and Reactors.
• Busbar Contacts & Joints and Bushings.
• Power Cables, Relays, and Circuit Breakers.
DESCRIPTION
The AWRMS™ 200 can be used in either stand alone or in conjunction with the MIL series of AccuLoss™ Loss Measurement Systems. The system is capable of performing both cold and hot resistance measurements on winding resistance.
Built into a steel enclosure on wheels the AWRMS™ 200 can be moved about easily and effortlessly. Two current cables and six potential cables are available for connection to the UUT. Standard cable length is 20 m. Cables up to 30 m and longer are available at time of order. The current and potential cables are supplied with clips (insulated and color coded for each channel) for easy connection to the poles of the transformer (UUT). Additional cables are available as an option.
14 PT100’s and 6 thermocouples come standard with optional expandability for up to 40 for measuring both oil and case temperatures. At the time of order, you can choose your configuration of either oil or case mounted.
All measurements are fully automatic and require no adjustments. The measurements are performed in accordance to the IEEE, IEC and other international standards.
Several safety circuits are built into the AWRMS™ 200 including overvoltage protection on the output of the DC Power Supply.
AWRMS™ FEATURES
Measurement Capabilities:
A source compliance of up to 100 Vdc @ 250 A (continuously variable) is used for measuring the winding resistance. The hot resistance is automatically temperature compensated for copper and aluminum windings (using a standard or customized reference temperature).
System Accuracy:
4-Wire Measurement Technique allows the use of long measurement leads for measuring the winding resistance without sacrificing accuracy. (See System Specifications).
Operating Convenience:
The system is computer controlled and fully automated for all measurements. There is no manual intervention required when operating in the Auto Mode.
Exceptional Reliability:
The components used in the AWRMS™ 200 are of the highest quality, and designed and manufactured for a rugged environment.
Rack Design:
The measuring units of the transformer test system are placed in a 19″ cabinet on wheels. This makes the AWRMS™ 200 easily movable. An industrial grade controller, monitor and keyboard are also located in the rack. An optional control desk is available if required.
Industry Preference:
In addition to the innovative technology, the AWRMS™ 200’s speed and accuracy account for the increased interest among many well known transformer and reactor manufactures.
BENEFITS
Modern Technology:
State of the art technology that will meet todays and future testing requirements.
Fast Measurements:
Measurements on the primary and secondary of the three phase UUT are done simultaneously. Power supply (max: 100 Vdc & 250 A), handle even the largest PTs and saturates them within the shortest time them within the shortest time.
Operating Efficiency:
A wide range of features specifically tailored for the testing of large PTs are accomplished through a 20 Channel Scanner. This ensures that all the temperature measurements are automated improving operator efficiency and eliminating human errors.
Safety:
Several safety circuits are built into the AWRMS™ 200 including:
1) Safety Foot Pedal.
2) Start Key Switch.
3) Start Button.
4) Magnetic Switch on the rear panel.
5) Heavy Duty Protection Circuit.
6) Warning light on top of the Rack.
7) Heavy Duty overvoltage protection at the Potential Terminals.
8) Emergency Stop Switch.
9) Software Warnings are shown on the screen.
1) After Selecting Cold or Hot Resistance Measurements.
2) After selecting OK and the measurement starts the message “Danger: Transformer Energized.
Do Not Touch Connections” is displayed.
10) The Test Current and Voltage for the power supply are selected automatically via the program.
Cost Reduction:
The AWRMS™ 200 is a multi-parameter rack system. Its automated operation improves measurement efficiency and reduces testing cost. The system can very much reduce the maintenance and unexpected shutdown costs.
INPUT CONNECTIONS
Input connections are made at the rear of the rack including current leads, potential leads and temperature leads. Both the current and potential leads are self locking once installed.
Two handles are used to move the system about from one transformer to another making the AWRMS™ 200 very flexible and portable.
Current Cables:
Current Cables are size 4/0 and are colour coded red for positive and black for negative with locking connectors when inserted into the rear panel plugs.
Potential Cables:
Six (6) #6 cables are included with the system with locking connectors when inserted into the rear panel plugs.
Calibration & Verification:
Items that are available to Calibrate the AWRMS™ 200 include the MIL Standard Resistor models 9332/0.0001, 0.001, 0.01, and 0.1 Ω and model 9331 10 Ω. The system is supplied with a calibration report using an 100 µΩ shunt at currents of 50, 100, 150 and 200 Amps.